Safety across the board

The DLF150 linear smoke detector

DLF150 linear smoke detector

How it works

The DLF150 linear smoke detector is specially designed for monitoring fire outbreaks over large areas. Thanks to an infrared beam – invisible to the human eye – between the transmitter unit and reflectors (prism mirror), the detector can quickly identify smoke build-up in the monitoring area and trigger an alarm. As smoke builds up or aerosol levels increase, these particles pass across the infrared beam, obscuring the reflected light signal. This change in light signal is evaluated by the transmitter unit and the alarm triggered if necessary.

The key planning requirements for this type of detector are set out in DIN VDE 0833-2 and other applicable standards. Under these standards, linear smoke detectors can be installed at a height of up to 16 m and the monitoring area is limited to 1400 m2.

The distance between the transmitter unit and the reflectors must be between 8 m and a maximum of 150 m.

Reflektoren

Use Cases

Linear smoke detectors are ideal for monitoring large internal spaces, such as halls and production facilities, where the time and costs associated with installing and maintaining point fire detectors would be very high due to the production downtimes involved.

They are also an excellent choice for buildings where the installation of point fire detectors is not permitted, such as historical buildings with decorative ceilings or premises where the ceiling height is over 12 m.

  • Large halls
  • Tunnels
  • Shopping centres
  • Listed buildings (e.g. museums and churches)
  • Aircraft hangers
  • Atriums
  • Libraries

Spotlight

Product

DLF150 linear smoke detector

The DLF150 linear smoke detector is available in two versions – with and without integrated heating. The version with integrated heating is highly recommended for locations where the detector will be subject to low temperatures and condensation.

comparison svg
  • Operating voltage: 21 to 28.8 V DC
  • Option (heating)
    - Power supply: 21 to 28.8 V DC
    - Current consumption: max. 650 mA
  • Contact load:
    - ALARM relay: max. 30 V / 2 A
    - FAULT relay: max. 30 V / 2 A
  • Range: 8 m to 150 m
  • Wiring: 0.5 to 2.5 mm2
  • Ambient temperature: -10 °C to +55 °C
  • Air humidity: max. 93% RH
  • Dimensions: 211 mm x 156 mm x 86 mm
  • Weight: 820 g
  • IP rating: IP54
  • VdS approval: pending

APP-based control

Android and iOS compatible

The new ‘DET-init’ app is a versatile and effective tool for commissioning the DLF150 linear smoke detector and performing servicing and maintenance tasks.

The view from the infrared camera on the transmitter unit is displayed in the app, so that users can precisely adjust the alignment between the transmitter unit and any paired reflectors. Any potential disturbances, e.g. reflective items in close proximity to the reflectors, can be easily identified and removed.

Brochure
DLF150 linear smoke detector

Additional information

Information about the new linear smoke detector and all its key features can be found in the product brochure.

Download

Video tutorial
DLF150 linear smoke detector

Commissioning and configuration guide

This short video explains how to commission the detector using the ‘DET-init’ app and establish a connection with the fire alarm control panel.

View

Service at it´s best

Project development and planning support

s

We will be happy to help with any queries or challenges you may have when it comes to fire alarm technology and voice alarms. As a direct point of contact, you can rely on us for excellent advice tailored to you.

Contact

These are your contacts

Service at it´s Best means making sure that your contacts are here for you whenever you need them and providing expert support and advice tailored to you.

An der Strusbek 19 Sketch